Welcome to visit Baoding Zhuoyue Electric Co.,LTD.!
switch 中文  |   switch English
Hotline:
+86-312-3136236/3021783
Your location:Home > Product > Comprehensive
Comprehensive

Zydr-2000 automatic capacitance inductance tester

Add time:2022-04-15   Number of views:499  

I. Product Overview

In order to reduce reactive power loss, shunt capacitor banks are usually used to improve power factor in power systems. In practical application, the accident rate of capacitor compensation device is relatively high, which is determined by the characteristics of the working state of capacitor device. Therefore, it is very important to detect the capacitor device regularly, find the defects of the capacitor early, and avoid the expansion of the fault.

But in the field capacitors are grouped in parallel, so the general capacitance meter needs to be removed after the lead can be measured, the workload is large, and easy to cause wiring errors. For this reason, our newly developed capacitive inductance tester can measure a single capacitor in a group of shunt capacitors without disassembling wires, and also measure inductance and current. Convenient wiring, simple operation, reduce the workload of maintenance personnel, greatly improve the field test efficiency, for the normal operation of the power grid to provide a guarantee.

Two, technical parameters

Measuring range capacitance: 0.1uF ~ 3300uF

Inductance: 0.1MH ~ 10000mH

Current: 0.1mA ~ 1A

Measuring accuracy capacitance: ±(1% reading +5 words)

Inductance: ±(1% reading +5 words)

Current: ±(1% reading +2 words)

Test power supply maximum: 8.4V·1A (constant current voltage limit)

Dimensions 345mm×295mm×175mm

The instrument weighs 4kg

Ambient temperature -10 ° C to 50 ° C

Ambient humidity ≤85%RH